Windings ສໍາລັບອຸປະກອນໄຟຟ້າຄວາມປອດໄພເພີ່ມຂຶ້ນ

ໃນອຸປະກອນໄຟຟ້າທີ່ປັບປຸງຄວາມປອດໄພ, ເຊັ່ນມໍເຕີປ້ອງກັນການລະເບີດ, ເຄື່ອງຫັນ, ສາຍແມ່ເຫຼັກໄຟຟ້າ, ແລະ ballasts ສໍາລັບໂຄມໄຟ fluorescent, ສ່ວນຫນຶ່ງປະກອບມີ windings ພາຍໃນ. ຄວາມຕ້ອງການສໍາລັບ windings ເຫຼົ່ານີ້, ທັງທາງກົນຈັກ ແລະທາງໄຟຟ້າ, ແມ່ນສູງກວ່າທີ່ສໍາລັບ windings ມາດຕະຖານ.


ໂດຍທົ່ວໄປ, ສາຍ insulated ທີ່ໃຊ້ສໍາລັບການ winding ວົງເຫຼົ່ານີ້ຄວນຈະເປັນສອງ insulated, and the coil’s rated diameter must not be less than 0.25mm.

For the enameled wire used in winding these coils, it is recommended to use GB/T6109.2-2008Polyester Enameled Round Copper Wire, Class 155,” GB/T 6109.5-2008 “Polyester-imide Enameled Round Copper Wire, Class 180,” GB/T 6109.6-2008 “Polyimide Enameled Round Copper Wire, Class 220,or GB/T6109.20-2008Polyamide-imide Composite Polyester or Polyester-imide Enameled Round Copper Wire, Class 220.

ນອກຈາກນັ້ນ, ເກຣດ 1 enameled round copper wire as specified in these standards can be used, provided it passes the relevant tests outlined in the standards.

After winding, an appropriate impregnating agent should be used to enhance the insulation properties of the windings.

The impregnation process should follow the manufacturer’s specified method, using techniques like dipping, trickling, or vacuum pressure impregnation (VPI) to fill the gaps between winding wires and ensure strong adhesion. If the impregnating agent contains solvents, the impregnation and drying should be performed twice to allow solvent evaporation.

ໂດຍທົ່ວໄປ, methods like spraying or coating for insulating windings are considered unreliable for ອຸ​ປະ​ກອນ​ໄຟ​ຟ້າ​ລະ​ເບີດ​. Adequate attention should be given to this in engineering practice.

ຍິ່ງໄປກວ່ານັ້ນ, for high-voltage windings, the impregnated windings should be treated with anti-corona paint to prevent additional hazards caused by corona discharges.

In enhanced-safety electrical devices, whether motors, electromagnetic coils, or other equipment’s coils, they should generally be equipped with ອຸນ​ຫະ​ພູມ protection devices to prevent exceeding limit temperatures under normal operation or recognized abnormal conditions.

If a winding does not exceed the limit temperature under continuous overload (such as a motor rotor lock), or if a winding is not subject to overload (like a ballast for fluorescent lamps), then it does not require a temperature protection device.

When enhanced-safety electrical equipment is equipped with temperature protection devices, these can be installed either internally or externally. Regardless, the protection device should have the appropriate ປະເພດລະເບີດ and should be assessed in conjunction with the protected equipment.