23 Година Индустријски произвођач отпоран на експлозију

+86-15957194752 аурорацхен@схенхаи-ек.цом

Уземљење електричне опреме отпорне на експлозију

1. Within regions prone to explosions, it is imperative that the enclosures of electrical equipment are securely connected to the grounding system.

grounding of explosion proof electrical equipment
2. When selecting уземљење wires for electrical equipment, multi-strand soft copper wires, with a cross-sectional area of at least 4 square millimeters, are recommended.

3. Ин експлозивно hazard areas, the principal grounding conductors should connect to the grounding body from various directions, ensuring a minimum of two distinct connections.

Caution: The use of pipelines carrying запаљиво gases or liquids as grounding conductors is strictly forbidden.

Прев: