23 Yil sanoat portlashdan himoyalangan ishlab chiqaruvchi

+86-15957194752 aurorachen@shenhai-ex.com

WindingsforIncreasedSafetyElectricalEquipment|Texnik spetsifikatsiyalar

Texnik spetsifikatsiyalar

Xavfsizlikni oshirish elektr jihozlari uchun sariqlar

Kengaytirilgan xavfsizlik elektr jihozlarida, portlashdan himoyalangan motorlar kabi, transformatorlar, elektromagnit simlar, va lyuminestsent lampalar uchun balastlar, bir qismi ichki sariqlarni o'z ichiga oladi. Ushbu o'rashlarga qo'yiladigan talablar, ham mexanik, ham elektr, standart o'rashlarga qaraganda yuqori.


Umuman, bu rulonlarni o'rash uchun ishlatiladigan izolyatsiyalangan sim ikki marta izolyatsiyalangan bo'lishi kerak, and the coil’s rated diameter must not be less than 0.25mm.

For the enameled wire used in winding these coils, it is recommended to use GB/T6109.2-2008Polyester Enameled Round Copper Wire, Class 155,GB/T 6109.5-2008 “Polyester-imide Enameled Round Copper Wire, Class 180,GB/T 6109.6-2008 “Polyimide Enameled Round Copper Wire, Class 220,or GB/T6109.20-2008Polyamide-imide Composite Polyester or Polyester-imide Enameled Round Copper Wire, Class 220.

Qo'shimcha, Baho 1 enameled round copper wire as specified in these standards can be used, provided it passes the relevant tests outlined in the standards.

After winding, an appropriate impregnating agent should be used to enhance the insulation properties of the windings.

The impregnation process should follow the manufacturer’s specified method, using techniques like dipping, trickling, or vacuum pressure impregnation (VPI) to fill the gaps between winding wires and ensure strong adhesion. If the impregnating agent contains solvents, the impregnation and drying should be performed twice to allow solvent evaporation.

Umuman, methods like spraying or coating for insulating windings are considered unreliable for portlashdan himoyalangan elektr jihozlari. Adequate attention should be given to this in engineering practice.

Bundan tashqari, for high-voltage windings, the impregnated windings should be treated with anti-corona paint to prevent additional hazards caused by corona discharges.

In enhanced-safety electrical devices, whether motors, electromagnetic coils, or other equipment’s coils, they should generally be equipped with harorat protection devices to prevent exceeding limit temperatures under normal operation or recognized abnormal conditions.

If a winding does not exceed the limit temperature under continuous overload (such as a motor rotor lock), or if a winding is not subject to overload (like a ballast for fluorescent lamps), then it does not require a temperature protection device.

When enhanced-safety electrical equipment is equipped with temperature protection devices, these can be installed either internally or externally. Regardless, the protection device should have the appropriate portlashga chidamli tur and should be assessed in conjunction with the protected equipment.